NEC Chapter 9. Checks the 40% fill limit for 3 or more conductors in a raceway.

Conduit Fill (NEC Ch. 9)

Wires

NEC conduit fill limits

  • 1 conductor: 53% fill allowed
  • 2 conductors: 31% fill allowed
  • 3+ conductors: 40% fill allowed (most common)

This calculator uses the 40% rule for 3+ conductors per NEC Chapter 9, Table 1.

Wire cross-sectional areas (NEC Annex C)

  • 14 AWG0.0097 in²
  • 12 AWG0.0133 in²
  • 10 AWG0.0211 in²
  • 8 AWG0.0366 in²
  • 6 AWG0.0507 in²
  • 4 AWG0.0824 in²

THHN/THWN-2 insulation. Values from NEC Table 5.

Common conduit sizes

  • ½" conduit0.196 in²
  • ¾" conduit0.384 in²
  • 1" conduit0.660 in²
  • 1¼" conduit1.084 in²
  • 1½" conduit1.502 in²
  • 2" conduit2.642 in²

EMT trade sizes. Internal area from NEC Chapter 9, Table 4.